Scope of application

DW15 Air Circuit Breaker or called ACB circuit breaker (hereinafter referred to as circuit breaker) is suitable for distribution networks with AC 50Hz, rated current 200A to 4000A and rated operating voltage from 380V to 1140V. The ABC circuit breaker is mainly used for power distribution and circuit protection in distribution networks, overload, under voltage and short circuit protection of power equipment.
Under normal conditions, the circuit breaker can be used as infrequent switching of the circuit and infrequent start of the motor.
TAIXI is a professional air circuit breaker suppliers, DW15 ABC circuit breaker complies with the GB14048.2.

Model and meaning

Model and meaning

● According to the use category

Class A (non-selective, with overcurrent two section protection).

● According to the transmission device

a. The front handle directly drives;
b. Motor drive.
Note: Unless specified by the user, normal supply has two functions of a and b.

● According to the release type

a. Overcurrent release and shunt release;
b. Overcurrent release, undervoltage instantaneous release;
c. Overcurrent release, shunt release and undervoltage instantaneous release.

● According to the type of overcurrent protection

a. Instantaneous operation of overload and short circuit (electromagnetic);
b. overload long delay and short-circuit instantaneous operation (thermal-electromagnetic);
Note: Users can consult with suppliers when they do not need overcurrent release.

● According to the type of undervoltage protection

a. Instantaneous operation;
b. Delay operation.

● According to the pre-energy storage

a. No pre-storage energy (energy storage and closing operations completed once);
b. Pre-stored energy (energy storage and closing operations completed twice).

● According to the way of inlet-outlet

a. Front-panel inlet-outlet (vertical inlet-outlet);
b. Back-panel inlet-outlet (horizontal inlet-outlet);
c. Front-panel inlet, back-panel outlet (vertical inlet, horizontal outlet);
d. Front-panel outlet, back-panel inlet (vertical outlet, horizontal inlet).

Normal working conditions

1. The ambient air temperature is -5°C to +40°C and the average value within 24 hours does not exceed +35°C. 2. The elevation of the installation site does not exceed 2000m.
3. Atmospheric relative humidity does not exceed 50% at ambient air temperature of +40°C; higher relative humidity at lower temperatures; monthly average maximum relative humidity of the wettest month is 90%, at the same time the average minimum temperature of the month is +25°C, and the condensation on the surface of the product due to the temperature change is considered.
4. Pollution level 3
5. Main circuit installation category of circuit breaker is IV. The auxiliary circuit installation category except for the undervoltage release coil, the installation category is the same as the main circuit of the breaker, the others are installation category III.

Main parameters and technical performance

1. The rated insulation voltage of this series of products is equal to the corresponding rated operating voltage.
2. The main parameters of the ABC circuit breaker

Frame rated current Inm (A) 630 1600 2500 4000
Conventional thermal current Ith (A) 200 400 630 1000 1600 2500 4000
Pole 3 3 3 3 3 3 3
Rated current In (A) Thermal electromagnetic 200 315, 400 315, 400, 630 630, 800, 1000 1250, 1600 1600, 2000, 2500 2500, 3000, 4000
Rated limit short circuit breaking capacity Icu (KA) AC 380V 30 30 30 40 40 60 60
Rated operation short circuit breaking capacity
Ics (KA)
AC 380V 30 30 30 30 30 40 50
Mechanical life (times) 10000 10000 10000 5000 5000 5000 4000
Electrical life 1In, 1Ue(times) 1000 1000 1000 500 500 500 500
Electrical life 1In, 1Ue(times) 1000 1000 1000 500 500 500 500
AC380V Protection motor life AC-3(times) 2000 2000 2000        
Operating frequency (times/h) 60 60 60 20 20 20 10
Arc distance (mm) 280 280 280 350 350 350 400
Operating arm (mm) 90 90 90 250 250 250 250
Operating force (N) 200 200 200 200 350 350 350

Note:
a. Rated short circuit breaking capacity of DW15 ACB circuit breaker, Inm≤630: the upper line, Inm>630: the same as the upper and lower lines.
b. The basic parameters of air circuit breaker DW15C-200, 400, 630 are the same as those of DW15-200, 400, 630.

3. ACB circuit breaker Release, Releasing Solenoid Coils and Control Box Rated Voltage

Type Rated voltage (V)
AC 50Hz DC
Release Shunt release Us 127, 220, 380 110, 220
Undervoltage release Us 127, 220, 380 -
Closing device Operating mechanism release energy electromagnet Us 127, 220, 380 110, 220
Operating electromagnet control box Us 220, 380
Motor Us 220, 380
Note: a. 127 specifications for mining.
b. If the operating solenoid control box with Us 660V is required, the user shall agree with the manufacturer.

Structure

1. DW15-200, 400, 630 Universal Circuit Breakers The DW15 ACB circuit breaker is a three-dimensional surface layout, and the contact system, the fast electromagnet, the left and right side panels are all mounted on an insulating plate. The upper part is equipped with an arc extinguishing system, and the operating mechanism can be mounted on the front or right side. There are "ON", "OFF" indication and manual off buttons. There is a shunt release at the upper left and an undervoltage release connected to the trip axle at the back. The speed saturation and current transformer are placed on the lower bus. Undervoltage delay devices and thermal relays are respectively below. The product structure is shown in Figure 1. 2. DW15-1600, 2500, 4000 Universal Circuit Breakers The ACB circuit breaker is a three-dimensional layout, contact system, the operating mechanism are installed on the iron frame. There is an arc extinguishing system on the upper part and an operating mechanism on the right. There are "ON", "OFF" indications and manual "open", "close" buttons. The left is equipped with shunt release and undervoltage release. The speed saturation and current transformer are placed on the lower bus. Undervoltage delay devices and thermal relays are installed below. The product structure is shown in Figure 2. 3. DW15C-200, 400, 630 Drawer ACB circuit breaker. The product consists of a breaker body (modified DW15) and a drawer seat. The ACB circuit breaker is equipped with a isolation contact knife, a dual circuit dynamic contact, and a ground contact support rail. The left and right panels of the drawer seat, aluminum brackets, isolation contact bases, dual circuit static contacts, sliders and other components. A push pull operation mechanism at the bottom is composed of an operation handle, a screw, etc.


Figure 1: Structure diagram of DW15-200, 400, 630 universal breakers

Figure 2: Structure diagram of DW15-1600, 2500, 4000 Air Circuit Breaker

Outline and Installation Dimension

Figure 3: Outline and installation dimensions of DW15-200~630 front operation Air Circuit Breaker

Figure 4: Outline and installation dimensions of DW15C-200~630 drawer circuit breaker

Figure 5: Outline and installation dimensions of DW15-1000~1600 Air Circuit Breaker

Figure 6: Outline and installation dimensions of DW15-2500 Air Circuit Breaker

Figure 7: Outline and installation dimensions of DW15-4000 Air Circuit Breaker